Total Production Tons | 4,540.00 |
Electric Production Tons | 1,943.07 |
Absorbtion Production Tons | 3,378.98 |
Thermal Storage Tons | 2,585.00 |
Total Consumption Tons | 4,062.00 |
Wet Bulb Temperature | 52.40 |
Dry Bulb Temperature | 57.60 |
System Makeup | 2.16 |
Production Tons | 0.00 |
KW / Ton | 1.00 |
Leaving CHW deg F | 43.50 |
Entering CHW deg F | 57.50 |
Supply Header from CT | 62.20 |
Discharge Header to CT | 62.00 |
Instrument Air Supply PSIG | 68.20 |
Trasar Level | 157.00 |
1-Inch Makeup | 0.10 |
3-Inch Makeup | 0.00 |
Production Tons | 0.00 |
CHW Distribution Diff PSI | 5.73 |
Leaving CHW degF | 45.00 |
Entering CHW degF | 47.30 |
Supply Header from CT | 61.80 |
Discharge Header to CT | 67.90 |
Instrument Air Supply PSIG | 78.98 |
Trasar Level | 50.05 |
South Makeup | 0.00 |
Production Tons | 1,934.00 |
KW/Ton | 0.00 |
Leaving CHW degF | 43.14 |
Entering CHW degF | 59.07 |
Supply Header from CT | 64.30 |
Discharge Header to CT | 72.80 |
Instrument Air Supply PSIG | 71.01 |
Trasar Level | 8.15 |
Cobb Makeup | 0.01 |
Production Tons | 0.00 |
Charge Tons | 0.00 |
Tank Percent Charged | 88.90 |
Leaving CHW degF | 42.60 |
Entering CHW degF | 51.80 |
Supply Header from CT | 58.10 |
Discharge Header to CT | 61.70 |
Tomkins Makeup | 0.01 |