Total Production Tons | 29,530.00 |
Electric Production Tons | 21,493.97 |
Absorbtion Production Tons | 3,378.98 |
Thermal Storage Tons | 0.00 |
Total Consumption Tons | 28,744.00 |
Wet Bulb Temperature | 75.00 |
Dry Bulb Temperature | 85.90 |
System Makeup | 0.72 |
Production Tons | 10,411.00 |
KW / Ton | 0.72 |
Leaving CHW deg F | 43.80 |
Entering CHW deg F | 55.30 |
Supply Header from CT | 81.40 |
Discharge Header to CT | 92.90 |
Instrument Air Supply PSIG | 68.50 |
Trasar Level | 162.00 |
1-Inch Makeup | 1.10 |
3-Inch Makeup | 0.00 |
Production Tons | 11,150.00 |
CHW Distribution Diff PSI | 5.73 |
Leaving CHW degF | 42.10 |
Entering CHW degF | 57.70 |
Supply Header from CT | 81.00 |
Discharge Header to CT | 90.30 |
Instrument Air Supply PSIG | 78.98 |
Trasar Level | 50.05 |
South Makeup | 0.00 |
Production Tons | 8,066.00 |
KW/Ton | 0.53 |
Leaving CHW degF | 43.14 |
Entering CHW degF | 59.07 |
Supply Header from CT | 81.10 |
Discharge Header to CT | 90.60 |
Instrument Air Supply PSIG | 71.01 |
Trasar Level | 8.15 |
Cobb Makeup | 0.01 |
Production Tons | 0.00 |
Charge Tons | 0.00 |
Tank Percent Charged | 5.40 |
Leaving CHW degF | 42.90 |
Entering CHW degF | 59.10 |
Supply Header from CT | 68.20 |
Discharge Header to CT | 70.80 |
Tomkins Makeup | 0.01 |